Six Unpatched Danfoss AK-SM800A Flaws Could Enable Remote Takeover

· Original article ↗

Summary

Researchers disclosed six unauthenticated AK-SM800A flaws, including one that enabled root code execution in testing. No fix or CVE IDs are available; researchers say firmware 5.4.0 remains affected, and agencies advise removing management interfaces from the internet.

Key points

  • Researchers classify all six flaws as pre-authentication stack-based buffer overflows.
  • One flaw in the root-running sm_app enabled remote code execution in testing on firmware 3.3.0; the researchers say it is also present in 5.3.2.
  • A separate flaw in sm_fcgi_app crashed the gateway in testing; code execution has not been demonstrated for that flaw.
  • Researchers say firmware 5.4.0 does not fix the flaws; BSI said it could not rule out that version being affected.
  • No CVE IDs, fixed firmware, or public proof of concept are available. BSI is not aware of active exploitation of these six flaws.
  • Researchers and agencies advise removing management interfaces from the internet and routing remote access through a VPN or private network; Strict mode alone is insufficient.
  • The article says the new flaws have not been linked to recent refrigeration-controller attacks, which reportedly used exposed panels, default credentials, and older fixed vulnerabilities.

Article Details

Vulnerability Types
  • Stack-based buffer overflow
Severity
BSI criticality 3 (Orange), rated for immediate action
Affected Versions
  • Danfoss AK-SM800A firmware 3.3.0
  • Danfoss AK-SM800A firmware up to and including 5.3.2
  • Danfoss AK-SM800A firmware 5.4.0; researchers say the flaws remain
Exploitation Status
not_reported
Exploit Availability
claimed_or_private
Patch Status
unavailable
Workarounds
  • Remove AK-SM800A management interfaces from direct internet access.
  • Route remote access through a VPN, private APN, or internal network.

MITRE ATT&CK