Utilities Need Fast, Controlled Remote Access to OT Systems

· Original article ↗

Summary

The article recommends framework-based OT remote access with approved, time-limited vendor sessions, named users, monitoring and safe shutdown. It cites attacks on water systems and warns that VPNs alone leave important access controls unaddressed.

Key points

  • The article says electric utilities follow mandatory NERC CIP standards, while water utilities face a proposed federal baseline and a patchwork of voluntary frameworks.
  • The FBI and EPA described attackers remotely reaching internet-facing water controllers and changing IP addresses and passwords; reported effects included loss of monitoring and control, pressure loss and flooding.
  • The article recommends measuring remote access against guidance such as NIST SP 1800-45, SANS ICS Critical Controls and American Water Works Association guidance.
  • It says VPN encryption and authentication do not address controls such as access approval, session review and incident response.
  • Recommended just-in-time access ties a vendor session to a named person, a specific asset and task, owner approval, and automatic closure when work ends.
  • Utilities should continuously review access, maintain IT/OT segmentation, place access platforms at the OT demilitarized zone and ensure they fail to a safe state.

Article Details

Defense Focus
Provide controlled, time-limited remote access to operational technology (OT) while enabling utilities to quickly deny or revoke unauthorized access.
Detection Methods
  • Continuously monitor access and review session recordings.
  • Use dashboard risk signals to inform session approval decisions; send raw logs to the security operations center.
  • Physically inspect the plant for cellular modems and cables that bypass hardened boundaries.
Data Sources
  • Remote-access logs
  • Session recordings
  • Dashboard risk signals
  • Physical inspection findings
Defensive Actions
  • Require approval for vendor access to a specific asset and task, and associate each session with a named person rather than a shared login.
  • Use just-in-time access that closes automatically when work ends; allow operators to isolate or disconnect sessions that behave unexpectedly.
  • Maintain the ability to cut external access quickly while continuing operations on local controls; ensure the access platform fails to a safe state.
  • Place the remote-access layer in the OT demilitarized zone at the IT/OT boundary, not at the controllers.
  • Review access procedures against applicable frameworks, document approvals, and maintain IT/OT segmentation.

MITRE ATT&CK

Vendors

Countries

Industries