Summary
The article recommends framework-based OT remote access with approved, time-limited vendor sessions, named users, monitoring and safe shutdown. It cites attacks on water systems and warns that VPNs alone leave important access controls unaddressed.
Key points
- The article says electric utilities follow mandatory NERC CIP standards, while water utilities face a proposed federal baseline and a patchwork of voluntary frameworks.
- The FBI and EPA described attackers remotely reaching internet-facing water controllers and changing IP addresses and passwords; reported effects included loss of monitoring and control, pressure loss and flooding.
- The article recommends measuring remote access against guidance such as NIST SP 1800-45, SANS ICS Critical Controls and American Water Works Association guidance.
- It says VPN encryption and authentication do not address controls such as access approval, session review and incident response.
- Recommended just-in-time access ties a vendor session to a named person, a specific asset and task, owner approval, and automatic closure when work ends.
- Utilities should continuously review access, maintain IT/OT segmentation, place access platforms at the OT demilitarized zone and ensure they fail to a safe state.
Article Details
- Defense Focus
- Provide controlled, time-limited remote access to operational technology (OT) while enabling utilities to quickly deny or revoke unauthorized access.
- Detection Methods
- Continuously monitor access and review session recordings.
- Use dashboard risk signals to inform session approval decisions; send raw logs to the security operations center.
- Physically inspect the plant for cellular modems and cables that bypass hardened boundaries.
- Data Sources
- Remote-access logs
- Session recordings
- Dashboard risk signals
- Physical inspection findings
- Defensive Actions
- Require approval for vendor access to a specific asset and task, and associate each session with a named person rather than a shared login.
- Use just-in-time access that closes automatically when work ends; allow operators to isolate or disconnect sessions that behave unexpectedly.
- Maintain the ability to cut external access quickly while continuing operations on local controls; ensure the access platform fails to a safe state.
- Place the remote-access layer in the OT demilitarized zone at the IT/OT boundary, not at the controllers.
- Review access procedures against applicable frameworks, document approvals, and maintain IT/OT segmentation.